Fire door monitor

Short Description:

This product is only a customer case product display, not for sale, and for reference only.

Manually and automatically close the normally open fire door; Monitor the status information of normally open or normally closed fire doors in real time, and report and display it.


Product Detail

Product Tags

Fire door control and condition monitoring function

Manually and automatically close the normally open fire door; Monitor the status information of normally open or normally closed fire doors in real time, and report and display it.

Networking
The monitor can be seamlessly connected to the Bluebird alarm controller; Fire door monitor can also be self-networking, networking monitor can be set as centralized machine or regional machine, centralized machine can control and display all regional machine, including cross-machine start regional machine fire door and display regional machine events and information, etc. It can receive CRT communication from central control room or fire alarm command from fire alarm controller.

Fire alarm receiving function
After the monitor is networked with fire alarm controller, it can be set to receive fire information from the fire alarm controller in selected real-time, so as to realize automatic control of the relevant fire doors. At the same time, the monitor will also automatically store the above alarm and linkage information.

Fault alarm function
In case of any problem with each function board card, power supply and various functional modules connected to the monitor, the monitor will report a fault at the first time. When the fire door is in an abnormal state, the monitor will also report faults at the first time, such as the normally closed fire door is in an abnormal open state, the normally open fire door is in an abnormal closed state, etc.

Door shielding and opening function
If a fire door is damaged during system operation, it can be shielded before the component is updated, and then opened after the component is updated. A shielded fire door cannot be controlled, and information about the shielded fire door is displayed on the monitor screen. As long as any part of the system is shielded, the shielded indicator light on the panel will be on.

Query function
You can query information from the query menu, including fire door annotation information, type and status of the online interface module, matching information between the module and the fire door, address segment for receiving fire alarms, and mapping between the fire door and the interface.

Information storage function
The monitor has the function of real-time storage of historical information, the maximum storage capacity is about 100000 pieces, you can query the monitor on, off, reset, fire alarm, various faults, fire door starting and other historical information.

Permission management
The monitor has two-level password permission management to ensure that the monitor is not mis operated.

Power management function
The monitor adopts a fire-fighting power supply with dual output function, which respectively supplies power for the monitor, on-site input/output interface module, and on-site electric door closers, electromagnetic releasers and other equipment; at the same time, the wall-mounted fire door It is also equipped with two backup batteries of DC12V/7AH, and the large-capacity fire door is equipped with two backup batteries of 12V/24Ah to ensure the continuous operation of the system;

Relay function
The monitor is equipped with 2 sets of output contacts, which output fault information and fire alarm information respectively.

Self-checking function
The monitor has a self-checking function.

Monitor appearance and internal structure diagram

2235

33555

Specification

JBF-61S20
Executive standards GB 29364-2012《Fire door monitor》
power per unit 252 points
System capacity Supports networking of up to 99 monitors. The system has a total capacity of 99×252 addressing points.
Manual operation key 1×60
Display function The monitor adopts 7-inch true color LCD.  Real-time display of system information, door events, faults, shielding, fire information and other information.
Information storage The maximum storage capacity is about 100000.
Authority management Secondary password authority management.
External interface Network、CAN、USB、RS232、Black box
Relay Two sets of relay output contacts. Output fault information and fire alarm information respectively.
Self check function With self-test function.
Main power Voltage in AC220V 85~110%. Frequency 50 ± 1Hz.
Main power capacity System power capacity 24V/2A. The capacity of auxiliary power supply (linkage power supply) is 24V/3A.
Standby power capacity two Section 12V/7Ah
Design power consumption 20W
Work environment 0℃~+40℃
Sound pressure level 65dB~85dB
Case size
(length×width×height)
440mm×124mm×540mm